Product details
The Fireray 5000-003 is the low-level system controller for the FFE Fireray 5000 motorized, auto-aligning reflective beam smoke detector, supplied separately as a spare or replacement. One controller runs and monitors up to two Fireray 5000 detector heads over a two-wire link, with separate fire and fault relays for each head.
Alignment, sensitivity and delay settings are made at the controller, which is mounted low so the detectors can be set up and tested from the ground.
Key features
- Controls up to two detector heads
- Separate fire and fault relays per detector
- 2-wire link to each detector, up to 100 m
- Logs the 50 most recent events per detector
- Programmable sensitivity and fire thresholds; adjustable delay to alarm and delay to fault
- 20 mm cable gland knockouts
Documents
Specifications
| Model | 5000-003 |
| Operating voltage | 14 to 36 VDC |
| Current, 1 detector | 5 to 6 mA (5.5 mA typical) |
| Current, 2 detectors | 7.5 to 8.5 mA (8 mA typical) |
| Current, alignment mode | 35 to 37 mA |
| Detectors per controller | Up to 2 |
| Controller-to-detector cable | 2 core, max. 100 m, 24-14 AWG (0.5-1.6 mm) |
| IP rating | IP54 |
| Housing flammability | UL94 V0 |
| Dimensions (with base) | 202 mm W x 230 mm H x 81 mm D (8.0 x 9.1 x 3.2 in) |
| Weight | 1.0 kg (2.2 lb) |
| UL file | S3417 |