Fireray 5000-104 Reflective Auto Aligning Beam Smoke Detector
Fireray 5000-104 Reflective Auto Aligning Beam Smoke Detector - image 2
Fireray 5000-104 Reflective Auto Aligning Beam Smoke Detector - image 3
Fireray 5000-104 Reflective Auto Aligning Beam Smoke Detector - image 4
Fireray 5000-104 Reflective Auto Aligning Beam Smoke Detector - image 5
Fireray 5000-104 Reflective Auto Aligning Beam Smoke Detector
Fireray 5000-104 Reflective Auto Aligning Beam Smoke Detector - image 2
Fireray 5000-104 Reflective Auto Aligning Beam Smoke Detector - image 3
Fireray 5000-104 Reflective Auto Aligning Beam Smoke Detector - image 4
Fireray 5000-104 Reflective Auto Aligning Beam Smoke Detector - image 5
Fireray 5000-104 Reflective Auto Aligning Beam Smoke Detector
Fireray 5000-104 Reflective Auto Aligning Beam Smoke Detector - image 2
Fireray 5000-104 Reflective Auto Aligning Beam Smoke Detector - image 3
Fireray 5000-104 Reflective Auto Aligning Beam Smoke Detector - image 4
Fireray 5000-104 Reflective Auto Aligning Beam Smoke Detector - image 5

Fireray 5000-104 Motorised Reflective Auto-Aligning Beam Smoke Detector, UL/FM, 8 m to 100 m

The Fireray 5000-104 is the UL and FM approved 8 m to 100 m model of the Fireray 5000 motorized reflective beam smoke detector range.

SKU: 5000-104

Free 30-Day Returns

Hassle-free returns

1-Year Warranty

Manufacturer warranty

Product details

The Fireray 5000-104 is the UL and FM approved 8 m to 100 m model of the Fireray 5000 motorized reflective beam smoke detector range.

The transmitter and receiver share one head and a passive prism returns the beam, so only one side of the protected area needs power and wiring. Smoke in the path weakens the returned signal, and an alarm is raised once obscuration exceeds the threshold. A laser is used to locate the prism, after which a motor steers the head and keeps it aligned as the building moves.

Key features

  • Motorized auto-alignment with laser prism location
  • One controller drives up to two heads, each with its own fire and fault relays
  • Adjustable threshold and alarm/fault delays
  • 850 nm optics in an IP54, UL94 V0 housing

Ordering note

Four reflectors are required for separations beyond 50 m, and a short range mask must be fitted below 18 m. The 5000-103 is the UL/FM 8 to 50 m version. The same hardware is sold as 5000-101/5000-102 (EN) and 5000-112/5000-113 (NF). A second head is the 5000-031.

Specifications

Model 5000-104
Range 8 m to 100 m
Approvals UL, FM; UL file S3417
Supply voltage 14–36 VDC
Current 5–6 mA (one head), 7.5–8.5 mA (two heads), 35–37 mA (aligning)
Alarm threshold 10 to 60% obscuration, 35% default
Alarm and fault delay 2 to 30 s
Wavelength 850 nm
IP rating IP54
Housing UL94 V0