Product details
The Honeywell 75267 is the RS-232 download cable used to send configurations from a PC to Gamewell-FCI E3 Series and S3 Series fire alarm control panels. One end lands on the panel's RS-232 screw terminal block through colour-coded flying leads, so a program built in CAMWorks can be downloaded on site.
Key features
- Colour-coded leads: red to RS-232 GND, black to TxD, green to RxD
- Same lead assignment on both E3 and S3 panel families
- On the first-generation ILI-MB-E3 the leads map to DB-9 pin 5 (GND), pin 2 (TxD) and pin 3 (RxD)
- Uses only the data terminals; the printer supervision terminal on the same block is left free
Ordering note
This is not the 75645 local ARCNET cable between ILI-MB-E3 boards, and it is not a printer cable. S3 panels can also be programmed through the SLP-E3 J2 Ethernet port.
Specifications
| Model | 75267 |
| Type | RS-232 programming / download cable |
| E3 Series connection | ILI-MB-E3 main board, TB6-1, TB6-2, TB6-4 |
| S3 Series connection | SLP-E3 main circuit, TB5-1, TB5-2, TB5-4 |
| Panel port rating | 15 VDC, 0.05 A max; up to 115.2 kbaud, 8 data bits, 1 stop bit, no parity |