Honeywell 75267 RS-232 Download Cable for E3 and S3 Series Panels

The Honeywell 75267 is the RS-232 download cable used to send configurations from a PC to Gamewell-FCI E3 Series and S3 Series fire alarm control panels. One end lands on the panel's RS-232 screw terminal block through colour-coded flying leads, so a program built in CAMWorks can be downloaded on site.

SKU: 75267

Available to order – usually ships in 1–3 weeks. Ask us for an exact lead time
Need a project quantity? Request a quote →

Free 30-Day Returns

Hassle-free returns

1-Year Warranty

Manufacturer warranty

Product details

The Honeywell 75267 is the RS-232 download cable used to send configurations from a PC to Gamewell-FCI E3 Series and S3 Series fire alarm control panels. One end lands on the panel's RS-232 screw terminal block through colour-coded flying leads, so a program built in CAMWorks can be downloaded on site.

Key features

  • Colour-coded leads: red to RS-232 GND, black to TxD, green to RxD
  • Same lead assignment on both E3 and S3 panel families
  • On the first-generation ILI-MB-E3 the leads map to DB-9 pin 5 (GND), pin 2 (TxD) and pin 3 (RxD)
  • Uses only the data terminals; the printer supervision terminal on the same block is left free

Ordering note

This is not the 75645 local ARCNET cable between ILI-MB-E3 boards, and it is not a printer cable. S3 panels can also be programmed through the SLP-E3 J2 Ethernet port.

Specifications

Model 75267
Type RS-232 programming / download cable
E3 Series connection ILI-MB-E3 main board, TB6-1, TB6-2, TB6-4
S3 Series connection SLP-E3 main circuit, TB5-1, TB5-2, TB5-4
Panel port rating 15 VDC, 0.05 A max; up to 115.2 kbaud, 8 data bits, 1 stop bit, no parity