Product details
The Gamewell-FCI ACM-30W is part of the Gamewell-FCI Elevate™ fire alarm platform. ACM-30 annunciator variant for Gamewell-FCI Elevate panels where the top LED for every switch is a fixed white LED; mounts in the GFP-BB-RA enclosure.
Annunciator Control Module Configurable for Activation and Indication. Customizable annunciator where the top LED for every switch uses a fixed white LED. Mounts remotely in GFP‑BB‑RA enclosure.
Key features
- Full-function annunciator: receives status and transmits commands to the panel
- 30 capacitive touch buttons, each with two color-programmable LEDs
- Independent or Cooperate mode per touchpoint
- Alarm/Circuit On and Trouble LED per point, or denser Alarm-only option
- Alarm and trouble resound with flash of new conditions
- Local piezo sounder with silence/acknowledge button
- System Trouble and On-Line/Power LED indicators
- Onboard end-of-line resistors enabled/disabled by switch
- Powered by 24 VDC from the panel or remote power supplies
- Slip-in custom labels or CAMWorks+ Tools labels
- Plug-in terminal blocks
Compatibility and documents
Works with: GFP-A, GFP-AR, GFP-BB-RA, GFP-BB-RAR, AIO-CBL
Differs from ACM-30 only in the fixed white top LED per switch (per official SKU text). Datasheet 9021-2195 covers ACM-30 generally; specs assumed shared - verify.
Lead time: typically ships in 2–3 weeks.
Specifications
| Model | ACM-30W |
| Platform | Gamewell-FCI Elevate |
| Buttons / LEDs | Capacitive touch keypad with 30 buttons, two LEDs each; header with 2 additional LEDs/buttons (On-Line/Power, System Trouble, Lamp Test, Silence/Acknowledge) |
| Product line description | 62 color-programmable Active, Trouble and Disabled LEDs, 32 momentary touchpoints, System Trouble LED, On-Line/Power LED, local piezo sounder |
| LED colors | red, green, yellow, white, amber, blue, cyan or purple |
| Point capacity | Up to 60 point indicators in Independent mode |
| Power requirements | 18-30VDC, 83mA standby current at 24VDC, 93mA alarm current at 24VDC (power-limited, non-resettable) |
| Communication | AIO bus (EIA-485 multi-drop, twisted pair) - 4 wires: 2 communication + 2 for 24 VDC |
| Max per FACP | Up to 10 as routers (panel datasheet: up to 80 annunciators per FACP) |
| Enclosure | GFP-BB-RA (grey) or GFP-BB-RAR (red) surface-mount enclosure |
| Terminals | Removable compression-type plug-in terminal blocks |
| Temperature and humidity | Operation 0-49°C/32-120°F; relative humidity 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F); recommended room temperature 15-27°C/60-80°F |
| UL/ULC Listed | S635 |
| FM Approved | FM23FPUS0095 |
| CSFM | 7165-0028:0516 |
| FDNY | COA#001761 |
| Seismic | IBC 2024: VMA-45894-01C |
| OSHPD | OSP-0072 |
| Standards | UL 864 10th edition; UL 2017; install per NFPA 72 |
| Country of origin | USA |