Gamewell-FCI AM-50-70 50 W 70.7 Vrms digital switching amplifier for E3 Series
Gamewell-FCI AM-50-70 50 W 70.7 Vrms digital switching amplifier for E3 Series - view 2
Gamewell-FCI AM-50-70 50 W 70.7 Vrms digital switching amplifier for E3 Series
Gamewell-FCI AM-50-70 50 W 70.7 Vrms digital switching amplifier for E3 Series - view 2
Gamewell-FCI AM-50-70 50 W 70.7 Vrms digital switching amplifier for E3 Series
Gamewell-FCI AM-50-70 50 W 70.7 Vrms digital switching amplifier for E3 Series - view 2

Gamewell-FCI AM-50-70 50 W 70.7 Vrms Digital Audio Amplifier for E3 Series

The Gamewell-FCI AM-50-70 is a 50 W digital switching power amplifier with a 70.7 Vrms output for E3 Series voice evacuation. It is used in the E3 Series Expandable Emergency Evacuation System, the Combined Fire and Mass Notification System and the Broadband Voice Evacuation System, under the control of an INI-VGX Transponder Voice Gateway.

SKU: AM-50-70

In stock – ships within 1 business day (2 available)
Need a project quantity? Request a quote →

Free 30-Day Returns

Hassle-free returns

1-Year Warranty

Manufacturer warranty

Product details

The Gamewell-FCI AM-50-70 is a 50 W digital switching power amplifier with a 70.7 Vrms output for E3 Series voice evacuation. It is used in the E3 Series Expandable Emergency Evacuation System, the Combined Fire and Mass Notification System and the Broadband Voice Evacuation System, under the control of an INI-VGX Transponder Voice Gateway.

Key features

  • Two speaker circuits, Style Y (Class B) or Style Z (Class A), sharing 50 W in total
  • Each circuit activated and supervised individually by the INI-VGX
  • Can broadcast sixteen messages generated by its local INI-VGX
  • Clear audio suited to live voice paging
  • UL 464 low-frequency compliance when used with selected System Sensor speakers and the 520 Hz audio profile

Installation notes

One INI-VGX node supports up to four AM-50 amplifiers of the same output voltage (150 W maximum across the four), so the AM-50-70 cannot share a node with an AM-50-25. Use the AM-50-PLATE extender when the panel works with the Autonomous Control Unit.

Also searched as: AM5070

Specifications

Model AM-50-70
Audio output 50 W max. at 70.7 Vrms (combined across both circuits)
Operating voltage 20.4 to 27.3 VDC
Standby current 0.049 A
Alarm current 2.30 A max. at 50 W
Field wiring Up to 12 AWG twisted-pair shielded
Operating temperature 32°F to 120°F (0°C to 49°C)
Humidity 0 to 93% RH, non-condensing at 90°F (32°C)
Dimensions 7-1/2" W x 3-1/2" H x 1-1/4" D (19 x 9 x 3 cm)
Standards UL 864 9th Ed., UL 2572, UL 464 low frequency
Listings UL S1869, FM 3017416, CSFM 7165-1703-0125, MEA FDNY COA# 6077