Product details
The Gamewell-FCI AMM-4SF is an addressable sub-loop monitor module that provides one address for a zone of conventional 2-wire smoke detectors. It has a single Style D (Class A) initiating circuit, also configurable as Style B (Class B) with an end-of-line resistor, and installs on the SLC of Gamewell-FCI analog addressable panels.
Key features
- Supports up to 20 conventional 2-wire smoke detectors
- Also accepts dry-contact devices such as heat detectors, manual stations, waterflow and tamper switches and 4-wire smoke detectors
- Stays in alarm with a single smoke detector activated
- Rotary decimal address switches, 01 to 159
- Bi-colour LED: green flash when polled, steady red in alarm (red only on non-Velociti panels)
Also searched as: AMM4SF
Specifications
| Model | AMM-4SF |
| Circuit | 1 IDC, Style D / Class A or Style B / Class B |
| Max. line resistance | 25 Ω |
| Detector capacity | Up to 20 two-wire smoke detectors |
| Mounting | 4" square box |
| Listings | UL S1949, UL 2572, FM 3023594, MEA FDNY 227-03-E |