Product details
The Gamewell-FCI ASD-PL3R-IV is a Velociti Series 3 plug-in intelligent photoelectric smoke sensor in ivory with remote test capability for duct applications. It runs on Velociti or CLIP protocol and is listed for use in ducts and inside DNR(W) duct smoke detector housings.
Key features
- Remote testing in DNR(W) housings with the RTS151 or RTS151KEY, no test coil needed
- Two panel-controlled LEDs, on, off or blinking in red, green or amber
- Output for an optional RA100Z remote LED annunciator
- Rotary address switches; point addressable up to 159 addresses
Installation notes
Wire the separately ordered base, set the address and remove power from the loop before fitting the sensor. Break the wire run at terminals 1 and 2 rather than looping it, so the connections stay supervised.
Also searched as: ASDPL3RIV
Specifications
| Model | ASD-PL3R-IV |
| Protocol | Velociti or CLIP |
| Colour | Ivory |
| Operating voltage | 15 to 32 VDC |
| Standby current | 200 µA at 24 VDC |
| Max. alarm current | 2 mA at 24 VDC; 4.5 mA max. with amber LED |
| Operating temperature | 32°F to 122°F (0°C to 50°C); -4°F to 158°F (-20°C to 70°C) in ducts |
| Humidity | 10 to 93% RH, non-condensing |
| Air velocity | 0 to 4,000 ft/min |
| Size | 2.0" (51 mm) high; 6.1" (155 mm) diameter in B300-6, 4.1" (104 mm) in B501 |
| Weight | 5.2 oz (147 g) |
| Duct listing | UL 268A |