Gamewell-FCI GWM34-72 local energy trip transmitter for coded alarm reporting - view 2
Gamewell-FCI GWM34-72 local energy trip transmitter for coded alarm reporting - view 3
Gamewell-FCI GWM34-72 local energy trip transmitter for coded alarm reporting - view 4
Gamewell-FCI GWM34-72 local energy trip transmitter for coded alarm reporting - view 5
Gamewell-FCI GWM34-72 local energy trip transmitter for coded alarm reporting - view 2
Gamewell-FCI GWM34-72 local energy trip transmitter for coded alarm reporting - view 3
Gamewell-FCI GWM34-72 local energy trip transmitter for coded alarm reporting - view 4
Gamewell-FCI GWM34-72 local energy trip transmitter for coded alarm reporting - view 5
Gamewell-FCI GWM34-72 local energy trip transmitter for coded alarm reporting - view 2
Gamewell-FCI GWM34-72 local energy trip transmitter for coded alarm reporting - view 3
Gamewell-FCI GWM34-72 local energy trip transmitter for coded alarm reporting - view 4
Gamewell-FCI GWM34-72 local energy trip transmitter for coded alarm reporting - view 5

Gamewell-FCI GWM34-72 Local Energy Trip Transmitter for Coded Alarm Reporting

The Gamewell-FCI GWM34-72 is a local energy trip transmitter for coded fire alarm reporting, built into a sheet metal housing with a plain door. When an interior fire alarm system trips it electrically, its three-fold spring-driven movement sends the box code over a normally closed series metallic municipal or industrial circuit. It has no means of manual operation and is supplied without test block, tap key or bell.

SKU: GWM34-72

In stock – ships within 1 business day (1 available)
Need a project quantity? Request a quote →

Free 30-Day Returns

Hassle-free returns

1-Year Warranty

Manufacturer warranty

Product details

The Gamewell-FCI GWM34-72 is a local energy trip transmitter for coded fire alarm reporting, built into a sheet metal housing with a plain door. When an interior fire alarm system trips it electrically, its three-fold spring-driven movement sends the box code over a normally closed series metallic municipal or industrial circuit. It has no means of manual operation and is supplied without test block, tap key or bell.

Key features

  • Gamewell-FCI three-fold spring-driven code movement
  • Sends four rounds of the box code per alarm
  • Local energy trip, operated by a local power source from the interior system
  • Sheet metal housing with plain door; no test block, tap key or bell

Installation notes

Run auxiliary circuit wiring in rigid conduit per the NEC. NFPA recommends locating the master box outside but close to the protected building, with lightning protection such as the GW 44551-01 arrester where lead-ins are aerial. Honeywell lists this local energy trip family as discontinued.

Also searched as: GWM3472

Specifications

Model GWM34-72
Type Local energy trip transmitter
Signaling circuit Normally closed series metallic, 0.100 A normal DC flow
Trip coil alarm current 0.250 A DC or 0.380 A at 60 Hz AC
Auxiliary supervisory current 0.050 A DC or 0.070 A at 60 Hz AC max
Nominal coil voltage 3.65 VDC or 50 VAC 60 Hz (use a series resistor for higher voltages)
Max. trip coil current 125% of nominal
Coil insulation 125 VAC (1,250 VAC breakdown test)