Gamewell-FCI GWPID-95 addressable point identification monitor module
Gamewell-FCI GWPID-95 addressable point identification monitor module - view 2
Gamewell-FCI GWPID-95 addressable point identification monitor module - view 3
Gamewell-FCI GWPID-95 addressable point identification monitor module - view 4
Gamewell-FCI GWPID-95 addressable point identification monitor module
Gamewell-FCI GWPID-95 addressable point identification monitor module - view 2
Gamewell-FCI GWPID-95 addressable point identification monitor module - view 3
Gamewell-FCI GWPID-95 addressable point identification monitor module - view 4
Gamewell-FCI GWPID-95 addressable point identification monitor module
Gamewell-FCI GWPID-95 addressable point identification monitor module - view 2
Gamewell-FCI GWPID-95 addressable point identification monitor module - view 3
Gamewell-FCI GWPID-95 addressable point identification monitor module - view 4

Gamewell-FCI GWPID-95 Addressable Point Identification Monitor Module

The Gamewell-FCI GWPID-95 (catalogue number PID-95) is an addressable point identification device, a monitor module that connects one non-powered, normally open dry contact to an analog addressable signaling line circuit. Typical inputs include water flow switches and conventional manual stations; when the contact closes, the module reports its address and the panel runs the outputs programmed for that point.

SKU: GWPID-95

In stock – ships within 1 business day
Need a project quantity? Request a quote →

Free 30-Day Returns

Hassle-free returns

1-Year Warranty

Manufacturer warranty

Product details

The Gamewell-FCI GWPID-95 (catalogue number PID-95) is an addressable point identification device, a monitor module that connects one non-powered, normally open dry contact to an analog addressable signaling line circuit. Typical inputs include water flow switches and conventional manual stations; when the contact closes, the module reports its address and the panel runs the outputs programmed for that point.

Key features

  • Monitors a single supervised Style B circuit to a dry contact device
  • Two-wire connection to the SLC
  • Address and priority interrupt set by DIP switch (priority interrupt on position 8)
  • Mounts in a 4" square back box with a blank cover plate

Compatibility

For Gamewell-FCI 600 Series and ILI95-E3 Series addressable panels. The PID-95P is a different version on a double-gang plate with a visible LED.

Also searched as: GWPID95

Specifications

Model GWPID-95 (PID-95)
Input Non-powered, normally open dry contact
Standby current 0.0005 A / 0.0008 A
Alarm current 0.0015 A
Operating temperature 32°F to 120°F
Humidity 93% non-condensing
Listings UL 864 9th Edition; UL S521; FM; FDNY; CSFM 7300-1703:0135