Product details
The Gamewell-FCI GWRCE-95 (RCE-95) is an addressable relay control element that lets a fire alarm panel operate building equipment such as door holders, elevator recall, dampers and motors. It provides dry relay contacts from the SLC and a feedback input, so the panel knows whether the controlled equipment actually changed state.
Key features
- Form-C dry contacts driven from the analog addressable SLC
- Feedback input confirms operation of the controlled equipment
- Two-wire, non-polarized SLC connection; Style 4, 6 or 7 wiring, fully supervised
- Integral LED indicates activation
- Address set by a single DIP switch
Compatibility
For Gamewell-FCI 600 Series and ILI95-E3 Series panels. Flush mounting needs trim ring 70839, sold separately; the optional RCD relay control display (one per eight elements) works only with IdentiFlex 632 and IF650.
Also searched as: GWRCE95
Specifications
| Model | GWRCE-95 (RCE-95) |
| Protocol | XP95 |
| Contact rating | 2.0 A at 30 VDC or 0.2 A at 120 VAC (2 A slow-blow fuse) |
| Power | 24 VDC from the analog circuit |
| Standby current | 0.0008 A |
| Alarm current | 0.0015 A |
| Mounting | Surface or flush in a standard 4.688" back box |
| Operating temperature | 32°F to 120°F |