Gamewell-FCI MCS-CO3 Addressable Carbon Monoxide Detector
Gamewell-FCI MCS-CO3 Addressable Carbon Monoxide Detector - view 2
Gamewell-FCI MCS-CO3 Addressable Carbon Monoxide Detector
Gamewell-FCI MCS-CO3 Addressable Carbon Monoxide Detector - view 2
Gamewell-FCI MCS-CO3 Addressable Carbon Monoxide Detector
Gamewell-FCI MCS-CO3 Addressable Carbon Monoxide Detector - view 2

Gamewell-FCI MCS-CO3 Intelligent Addressable Carbon Monoxide Detector

The Gamewell-FCI MCS-CO3 is an intelligent addressable carbon monoxide detector that brings system-connected CO monitoring onto the fire alarm addressable loop. It is used where fuel-burning equipment is present, and because each unit has its own address, the panel reports the exact location of a CO event.

SKU: MCS-CO3

Available to order – usually ships in 1–3 weeks. Ask us for an exact lead time
Need a project quantity? Request a quote →

Free 30-Day Returns

Hassle-free returns

1-Year Warranty

Manufacturer warranty

Product details

The Gamewell-FCI MCS-CO3 is an intelligent addressable carbon monoxide detector that brings system-connected CO monitoring onto the fire alarm addressable loop. It is used where fuel-burning equipment is present, and because each unit has its own address, the panel reports the exact location of a CO event.

Key features

  • CO-only sensing with drift compensation and RealTest testing
  • Velociti protocol, one address set with rotary switches
  • 10-year CO cell with end-of-life warning and fault
  • Plug-in head; bases ordered separately, and a B200S sounder base gives the Temp 4 CO pattern

Compatibility

Requires E3 Series 4.10, S3 Series 1.21 or NGA 4.01 firmware or later. Not the same as the MCS-COF3, which combines smoke, infrared, heat and CO sensing.

Also searched as: MCSCO3

Specifications

Model MCS-CO3
Protocol Velociti, 1 address
Operating voltage 15 to 32 VDC
Current at 24 VDC 200 µA operating; 2 mA alarm; 4.5 mA max
Response (UL 2034) 70 ppm in 60-240 min; 150 ppm in 10-50 min; 400 ppm in 4-15 min
Operating temperature 32°F to 122°F
Humidity 15% to 90% RH
Isolator load 0.0063
Listings UL 2075; UL S1195