Product details
The Gamewell-FCI MCS-COF3-IV is an ivory plug-in addressable detector that combines smoke, carbon monoxide, infrared and heat sensing on a single SLC address. Its algorithms weigh all four inputs to respond quickly to real fires while rejecting nuisance sources such as theater smoke, making it a strong choice for spaces with moderate to heavy nuisance conditions that also need CO detection.
Key features
- Photoelectric smoke, electrochemical CO, infrared light and thermal sensing in one head
- Heat and rate-of-rise sensing with a 135°F fixed threshold
- Reports fire and CO as separate signals while using one address
- 10-year CO cell with end-of-life warning
- Velociti SLC protocol
- Classic ivory finish
Installation notes
The base is ordered separately. A B200S series intelligent sounder base is recommended so fire (Temp 3) and CO (Temp 4) produce distinct tones; program the panel so a CO event is not annunciated as fire.
Also searched as: MCSCOF3IV
Specifications
| Model | MCS-COF3-IV |
| Protocol | Velociti, 1 address |
| Operating voltage | 15 to 32 VDC |
| Current at 24 VDC | 200 µA operating; 2 mA alarm; 4.5 mA max |
| CO response | 70 ppm: 60-240 min; 150 ppm: 10-50 min; 400 ppm: 4-15 min |
| Operating temperature | 32°F to 100°F (0°C to 38°C) |
| Humidity | 15% to 90% RH, non-condensing |
| Air velocity | 0 to 4,000 ft/min (0 to 1,219.2 m/min) |
| Size in B200S base | 2.7" H x 6.875" dia. (69 x 175 mm) |
| Weight | 3.4 oz (95 g) |
| Listings | UL 268 7th Edition; UL 521; UL 2075; UL S1195; CSFM 7272-1703:0508 |