Gamewell-FCI MMI-10F Ten-Input Multi-Mod Monitor Module
Gamewell-FCI MMI-10F Ten-Input Multi-Mod Monitor Module - view 2
Gamewell-FCI MMI-10F Ten-Input Multi-Mod Monitor Module - view 3
Gamewell-FCI MMI-10F Ten-Input Multi-Mod Monitor Module - view 4
Gamewell-FCI MMI-10F Ten-Input Multi-Mod Monitor Module
Gamewell-FCI MMI-10F Ten-Input Multi-Mod Monitor Module - view 2
Gamewell-FCI MMI-10F Ten-Input Multi-Mod Monitor Module - view 3
Gamewell-FCI MMI-10F Ten-Input Multi-Mod Monitor Module - view 4
Gamewell-FCI MMI-10F Ten-Input Multi-Mod Monitor Module
Gamewell-FCI MMI-10F Ten-Input Multi-Mod Monitor Module - view 2
Gamewell-FCI MMI-10F Ten-Input Multi-Mod Monitor Module - view 3
Gamewell-FCI MMI-10F Ten-Input Multi-Mod Monitor Module - view 4

Gamewell-FCI MMI-10F Ten-Input Multi-Mod Monitor Module for Velociti Series

The Gamewell-FCI MMI-10F is a Velociti Series Multi-Mod module with ten monitor inputs for Gamewell-FCI analog addressable SLCs. It provides ten Class B or five Class A supervised initiating circuits for normally open devices such as manual stations, waterflow, tamper and supervisory switches, heat detectors and 4-wire smoke detectors, and is designed for centralizing many circuits in one place.

SKU: MMI-10F

In stock – ships within 1 business day
Need a project quantity? Request a quote →

Free 30-Day Returns

Hassle-free returns

1-Year Warranty

Manufacturer warranty

Product details

The Gamewell-FCI MMI-10F is a Velociti Series Multi-Mod module with ten monitor inputs for Gamewell-FCI analog addressable SLCs. It provides ten Class B or five Class A supervised initiating circuits for normally open devices such as manual stations, waterflow, tamper and supervisory switches, heat detectors and 4-wire smoke detectors, and is designed for centralizing many circuits in one place.

Key features

  • Ten Style B (Class B) or five Style D (Class A) supervised IDCs, selected by jumper
  • Each circuit has its own SLC address for individual control-by-event programming
  • First address set on two rotary dials; the following addresses are assigned in sequence
  • Jumper matrix can disable up to two unused addresses
  • Status LED per circuit; removable terminal blocks for 12 to 18 AWG

Installation notes

Two modules fit in an MBB-2 back box, or up to six on an MCH-6 chassis in an MBB-6 cabinet. On panels not running in Velociti mode, only the red LED operates.

Also searched as: MMI10F

Specifications

Model MMI-10F
Operating voltage 15 to 32 VDC
Standby current 3.5 mA
Alarm current 60 mA with all ten LEDs lit
IDC limits 40 ohms max wire resistance; 12 VDC max; 1 mA max
Operating temperature 32°F to 120°F (0°C to 49°C)
Humidity 10 to 85% non-condensing
Dimensions 6.8" H x 5.8" W x 1.25" D (17.3 x 14.7 x 3.2 cm)
Listings UL 864 9th Edition; UL 2572; UL S1913; FM 3023594; FDNY 219-02-E Vol VI; CSFM 7300-1703:0124

You May Also Like