Product details
The Gamewell-FCI MS-7S is the single-action conventional pull station of the MS-7 Series. One pull operates a set of single-pole contacts on an initiating device circuit, so it works with any UL listed conventional control panel.
Key features
- Single-action operation
- Wire lead connections
- Meets the ADA 5 lb maximum pull force
- Operating instructions and Braille molded into the handle
- Tumbler lock keyed alike with Gamewell-FCI panels
Installation notes
Mounts surface or semi-flush on a double-gang or 4" square box. For outdoor locations use the MS-7LOB; for a double-action conventional station use the MS-7.
Also searched as: MS7S
Specifications
| Model | MS-7S |
| Operation | Single action, conventional |
| Contacts | Single pole, 0.25 A at 30 VAC/VDC (resistive) |
| Connections | Wire leads |
| Housing | Lexan |
| Dimensions | 5-5/8" H x 4-1/4" W x 1-1/4" D |
| Standard | Designed to UL 864 9th Edition |