Product details
The Gamewell-FCI TM-8 is part of the Gamewell-FCI Elevate™ fire alarm platform. AIO-bus transmitter module for Elevate GFP-A/GFP-AR panels with eight programmable Form-C relays plus either three reverse-polarity remote station outputs or a municipal box trip output.
Module with 8 programmable Form‑C relays (4×2A, 4×10A). Supports remote station service or municipal box connection and installs up to 6000 ft away on the AIO bus. High‑current relays support inductive loads.
Key features
- 8 programmable Form-C relays: four low-current, four higher-current
- Either three reverse-polarity outputs (alarm, trouble, supervisory) or fire municipal box trip
- Connects to the internal AIO bus and mounts inside the GFP-A/GFP-AR cabinet on the PMB's right-side option card position
- Loss of power or communication inherently supervised through AIO bus
- Diagnostic LEDs: green Power, AIO RX and TX; yellow Trouble
- Customizable 80-character primary label per module
- Relay 1 predispositioned as fail-safe trouble (reprogrammable)
- Higher-current relays can switch inductive loads (0.35PF)
- Remote Station Disconnect from panel display
- Isolated 24 V for remote station reverse-polarity outputs
- Designed to meet NFPA 72 for Auxiliary and Remote Station Protective Signaling Systems
Compatibility and documents
Works with: GFP-A, GFP-AR
Lead time: typically ships in 2–3 weeks.
Specifications
| Model | TM-8 |
| Platform | Gamewell-FCI Elevate |
| Relays | Eight (8) programmable Form-C relays |
| Low-current relays 1-4 (TB3-TB6) | 2A @ 30 VDC resistive |
| High-current relays 5-8 (TB7-TB10), resistive | 10A @ 28 VDC; 12A @ 125 VAC; 6A @ 250 VAC; 5A @ 277 VAC |
| High-current relays 5-8, inductive (0.35 PF) | 2A @ 28 VDC; 4A @ 125 VAC; 2A @ 250 VAC |
| Remote station outputs | Three isolated reverse polarity outputs; 15mA max per output; 24 VDC nominal |
| Municipal box trip (local energy) | Supervisory current 0.023 A; trip current 0.35 A |
| Standby current | 81mA @ 24 VDC |
| Alarm current | 189mA @ 24 VDC (all relays energized) |
| Power source | Filtered, non-resettable 24 VDC listed for fire-protective signaling |
| Board size | Approximately 4.375" (11.11cm) W x 7" (17.78cm) H |
| Distance | Up to 6000 ft from panel on RS485 (AIO) bus (per panel datasheet/SKU text) |
| Temperature and humidity | 0-49°C (32-120°F); 85% RH at 30°C (86°F) and 93% ± 2% at 32°C ± 2°C, non-condensing; recommended 15-27°C (60-80°F) |
| UL | Listed |
| FM | Approved |
| Country of origin | USA |
| Dimensions | Approximately 4.375" W x 7" H |