Product details
The Honeywell HON-DACT-DS DS Dialer is a dual-line digital alarm communicator transmitter (DACT) made up of a main board and POTS card in a separate red enclosure. It mounts outside the fire alarm control panel and sends events from a standalone panel or a panel network to a central station over the public telephone network.
Key features
- Two monitored POTS lines with line-voltage supervision
- Seizes the line and disconnects premises telephones sharing it when reporting
- Ademco Contact ID format; dial tone detection at 350 and 440 Hz
- Housed in its own enclosure rather than as a plug-in panel card
Compatibility
For NOTIFIER INSPIRE N16E and N16X; NOTIFIER ONYX NFS-320, NFS-640, NFS2-640, NFS-3030 and NFS2-3030; and Gamewell-FCI ILI-MB-E3, ILI95-MB-E3 and SLP-E3. Two RJ31X jacks, two MCBL-7 phone cords and a NUP serial cable (32351718-001, or kit 50160636-001) are ordered separately.
Also searched as: HONDACTDS
Specifications
| Model | HON-DACT-DS |
| Type | Dual-line DACT |
| Operating voltage | 18 to 30 VDC |
| Current | 200 mA at 18 V; 150 mA at 24 V |
| Dimensions | 10" H x 2-3/4" W x 8" L |
| Weight | 2 lb |
| Listing | ETL listed to UL 864 10th Edition (control number 5025335) |