Product details
The Honeywell TC822A1010 is a FlashScan dual monitor / dual relay ("two-in, two-out") module for Honeywell XLS intelligent addressable fire alarm panels. It combines supervision and control at one location, such as monitoring flow and tamper switches while operating a damper and a door holder, replacing two separate modules and a junction box.
Key features
- Two Class B monitored inputs and two Form C relay outputs
- FlashScan protocol on the two-wire SLC
- Rotary decade address switches
- Each input and relay is annunciated individually
Ordering note
Because each input and relay reports separately, the module uses more than one consecutive SLC address; check Honeywell document 74-5104 when planning the loop. Class A circuits are not supported. The ULC-listed version is TC822A1010CDN.
Specifications
| Model | TC822A1010 |
| Inputs | 2, Class B monitored |
| Outputs | 2 Form C relays |
| Protocol | FlashScan |
| Compatible panels | XLS120, XLS120C, XLS120E, XLS140-2, XLS3000 |
| Addressing | Rotary decade switches |