Product details
The Notifier FZM-1 is an addressable interface module that brings a zone of conventional two-wire smoke detectors onto an intelligent SLC loop.
Conventional two-wire detectors cannot respond to an addressable poll and need a separate 24 V supply. The FZM-1 monitors and supervises one zone of compatible two-wire detectors and reports it to the panel at a single address as normal, open or alarm. It replaces the MMX-2 in existing systems.
Key features
- Monitors a Style B (Class B) or Style D (Class A) initiating device circuit
- Single SLC address for the whole zone
- Rotary address switches
- 3.9 kohm end-of-line resistor supplied
Ordering note
Detectors must be UL compatible with the module. Do not substitute the FMM-1 (dry contacts on a 47 kohm EOL; cannot power two-wire detectors) or the FDM-1 (dual Class B monitor using two addresses).
Specifications
| Model | FZM-1 |
| Function | Two-wire smoke detector interface (monitor) module |
| Operating voltage | 15 to 32 VDC nominal |
| Maximum current draw | 5.1 mA (LED on) |
| Addressing | 01-159 FlashScan; 01-99 CLIP |
| EOL resistor | 3.9 kohm (supplied) |
| Maximum IDC wiring resistance | 25 ohms |
| External supply | 24 VDC power limited, 90 mA per module maximum |
| Mounting | 4 in. square x 2.125 in. deep electrical box |