Notifier FZM-1 Standard-Sized Module
Notifier FZM-1 Standard-Sized Module - image 2
Notifier FZM-1 Standard-Sized Module
Notifier FZM-1 Standard-Sized Module - image 2
Notifier FZM-1 Standard-Sized Module
Notifier FZM-1 Standard-Sized Module - image 2

Notifier FZM-1 Addressable Monitor Module for Two-Wire Smoke Detectors

The Notifier FZM-1 is an addressable interface module that brings a zone of conventional two-wire smoke detectors onto an intelligent SLC loop.

SKU: FZM-1

Free 30-Day Returns

Hassle-free returns

1-Year Warranty

Manufacturer warranty

Product details

The Notifier FZM-1 is an addressable interface module that brings a zone of conventional two-wire smoke detectors onto an intelligent SLC loop.

Conventional two-wire detectors cannot respond to an addressable poll and need a separate 24 V supply. The FZM-1 monitors and supervises one zone of compatible two-wire detectors and reports it to the panel at a single address as normal, open or alarm. It replaces the MMX-2 in existing systems.

Key features

  • Monitors a Style B (Class B) or Style D (Class A) initiating device circuit
  • Single SLC address for the whole zone
  • Rotary address switches
  • 3.9 kohm end-of-line resistor supplied

Ordering note

Detectors must be UL compatible with the module. Do not substitute the FMM-1 (dry contacts on a 47 kohm EOL; cannot power two-wire detectors) or the FDM-1 (dual Class B monitor using two addresses).

Specifications

Model FZM-1
Function Two-wire smoke detector interface (monitor) module
Operating voltage 15 to 32 VDC nominal
Maximum current draw 5.1 mA (LED on)
Addressing 01-159 FlashScan; 01-99 CLIP
EOL resistor 3.9 kohm (supplied)
Maximum IDC wiring resistance 25 ohms
External supply 24 VDC power limited, 90 mA per module maximum
Mounting 4 in. square x 2.125 in. deep electrical box