Notifier NFC-LOC Local Operator Console, Builtin Microphone, Message and Zone Control Switches, Black
Notifier NFC-LOC Local Operator Console, Builtin Microphone, Message and Zone Control Switches, Black - image 2
Notifier NFC-LOC Local Operator Console, Builtin Microphone, Message and Zone Control Switches, Black - image 3
Notifier NFC-LOC Local Operator Console, Builtin Microphone, Message and Zone Control Switches, Black
Notifier NFC-LOC Local Operator Console, Builtin Microphone, Message and Zone Control Switches, Black - image 2
Notifier NFC-LOC Local Operator Console, Builtin Microphone, Message and Zone Control Switches, Black - image 3
Notifier NFC-LOC Local Operator Console, Builtin Microphone, Message and Zone Control Switches, Black
Notifier NFC-LOC Local Operator Console, Builtin Microphone, Message and Zone Control Switches, Black - image 2
Notifier NFC-LOC Local Operator Console, Builtin Microphone, Message and Zone Control Switches, Black - image 3

Notifier NFC-LOC Local Operator Console, Builtin Microphone, Message and Zone Control Switches, Black

The Notifier NFC-LOC is an optional FirstCommand Local Operator Console for the NFC-50/100(E) emergency voice evacuation panel, used for fire protection and mass notification.

SKU: NFC-LOC

Free 30-Day Returns

Hassle-free returns

1-Year Warranty

Manufacturer warranty

Product details

The Notifier NFC-LOC is an optional FirstCommand Local Operator Console for the NFC-50/100(E) emergency voice evacuation panel, used for fire protection and mass notification.

One of a family of remote consoles that extend NFC-50/100(E) display and control to other locations in a building, it duplicates the main console operator interface and adds a built-in push-to-talk microphone for ALL CALL paging. It is housed in a black keyed cabinet to prevent unauthorized access.

Key features

  • Operator interface identical to the NFC-50/100(E) main console
  • Built-in push-to-talk microphone for ALL CALL paging
  • Fourteen programmable message buttons to activate all speaker circuits remotely
  • Up to eight NFC-LOCs per NFC-50/100(E)
  • Keyed lock cabinet; optional thumb lock
  • UL 864 listed and seismic certified

Ordering note

Requires external data bus, audio riser and 24 VDC operator interface power connections from the NFC-50/100 main console. For standby and alarm current and battery calculations, see the NFC-50/100(E) Product Manual P/N LS10001-001NF-E.

Specifications

Model NFC-LOC
Power 24 VDC non-resettable from the NFC-50/100(E) (external operator interface power, non-supervised)
Backbox 19.0 in. (48.26 cm) H x 16.65 in. (42.29 cm) W x 5.2 in. (13.23 cm) D
Door 19.26 in. (48.92 cm) H x 16.821 in. (42.73 cm) W
Trim ring (TR-CE-B) 22.00 in. (55.88 cm) H x 19.65 in. (49.91 cm) W
Shipping weight 18.44 lb (8.36 kg)
Color Black
Listings UL S635
Standards UL S635, UL 2572, UL 864; IBC 2000-2012 and CBC 2007 (seismic)