Product details
The Potter PAD200-PCD is an analog addressable photoelectric smoke and carbon monoxide detector head for panels using the Potter PAD protocol. It combines a photoelectric chamber that meets the UL 268 7th Edition enhanced sensitivity tests with an electrochemical CO cell listed to UL 2075, the standard for system-connected CO detectors, all on one address.
Key features
- Photoelectric smoke and electrochemical CO sensing in one head
- Address 1 to 127 set by DIP switch, no programming tool needed
- 10-year CO detection life with built-in end-of-life indication
- UUKL listed for smoke control
- Twists onto any PAD base
Ordering note
The base is ordered separately. The under-2-inch profile Potter quotes applies to the head on a PAD100-4DB or PAD100-6DB. The PAD200-PD is the photoelectric-only head, and the PAD200-PCHD adds a heat element.
Specifications
| Model | PAD200-PCD |
| Smoke alarm set point range | 1.1 to 3.5 %/ft. (3.6 to 11 %/m) |
| Power | 24 VDC, 300 µA |
| Start-up | 1 second |
| Address range | 1 to 127 |
| CO sensor life | 10 years |
| Air velocity (open area) | 0 to 300 ft/min |
| Max listed spacing | 30 ft |
| Environment | 32 to 120 °F, 0 to 93% RH |
| Color | Eggshell white |
| Dimensions | 1.35 in. high x 3.93 in. diameter |
| Listings | UL 268 7th Ed., UL 2075, UUKL |