Product details
The Potter PAD200-PHD is an analog addressable photoelectric smoke sensor with a built-in thermistor heat element, for panels using the Potter Addressable Device (PAD) protocol. It provides a 135 °F fixed-temperature heat alarm with selectable rate of rise.
The sensor twists onto a PAD series base, ordered separately, which carries the field wiring and any relay, isolator or sounder option. The panel and sensor monitor chamber condition together, compensating for drift and reporting a dirty sensor.
Key features
- Photoelectric smoke plus thermistor heat sensing
- Fixed 135 °F heat alarm with selectable 15 °F per minute rate of rise
- Drift compensation and dirty-sensor reporting
- DIP switch addressing, 127 addresses per loop
- UL 268 7th Edition; UUKL for smoke control
Ordering note
Compatible bases are the PAD100-4DB and PAD100-6DB standard bases, PAD100-IB isolator, PAD100-RB relay, PAD100-SB sounder and PAD100-SPKB speaker. In the PAD200 range, the PAD200-PD is smoke only, the PAD200-PCD swaps heat for carbon monoxide, and the PAD200-PCHD includes all three.
Specifications
| Model | PAD200-PHD |
| Smoke alarm set-point range | 1.1 to 3.5 %/ft |
| Heat | 135 °F fixed; 15 °F/min rate of rise (selectable) |
| Power | 24 VDC, 300 µA |
| Addresses per loop | 127 |
| Air velocity (open area) | 0 to 300 ft/min |
| Dimensions (without base) | 1.94 in. high x 3.93 in. diameter |
| Listings | UL 268 7th Edition, UUKL |
| Base | Not included |