Product details
The Potter PFC-4064 RB is the replacement main board assembly for the Potter PFC-4064 conventional fire alarm control panel. When a board is damaged by a surge or wiring fault, the cabinet, door and field terminations usually survive, so replacing only the board avoids a full panel re-installation.
Potter sells the board separately as item 3992363; the complete panel in its cabinet is item 3992360.
Key features
- Six programmable Class A or B input circuits, expandable to 192 with IDC-6 cards
- Four power-limited 3.0 A NACs with strobe sync
- One 1.0 A auxiliary output and four Form C relays
- 4 x 20 LCD, P-Link RS-485 bus, Ethernet and 4,000-event log
Ordering note
Board only: no cabinet, door or batteries are included. Allow time to re-enter the site program and re-test the system after replacement.
Specifications
| Model | PFC-4064 RB |
| Potter item | 3992363 (board); 3992360 = complete panel |
| Inputs | 6, Class A or B (to 192 with IDC-6) |
| NACs | 4 power-limited, 3.0 A each, strobe sync |
| Power supply | 5.0 A 24 VDC (NAC + aux load max 5.0 A) |
| Auxiliary output | 1 x 1.0 A |
| Relays | 4 Form C |
| Display | 4 x 20 LCD |
| Communication | P-Link RS-485, Ethernet |
| Event log | 4,000 events |
| AC input | 120/240 VAC 50/60 Hz, 2.5 A max |
| Battery circuit | 7–55 AH |
| Standards | UL-864, NFPA-70, NFPA-72 |
| Environment | Indoor only, 32° to 120°F |