Product details
The Potter RMS-6T-EXP-WP-LP-KL is an explosion-proof, dual-action manual fire alarm pull station with dual Form C contacts and a key-lock reset. Its die-cast explosion-proof housing provides the hazardous-location rating.
Reading the model code: 6T is the dual Form C (DPDT) contact block, EXP is explosion proof, WP is weatherproof, LP is the Lift and Pull dual-action cover, and KL is the key-lock reset in place of the standard hex-key reset.
Key features
- Dual-action Lift and Pull cover
- Key-lock reset
- DPDT switch with screw terminal strip
- Two 3/4 in. – 14 NPT conduit fittings
- UL listed, Marine rated, CSFM listed, MEA approved
Ordering note
Check the full suffix. The base RMS-6T-EXP-WP is single action without the Lift and Pull cover or key lock, and the DAH option uses a break-glass adapter instead of LP. The RMS-1T-WP specified for ordinary outdoor and wet locations is weatherproof only, not explosion-proof.
Specifications
| Model | RMS-6T-EXP-WP-LP-KL |
| Hazardous locations | Class I Groups B, C, D; Class II Groups E, F, G; Class III |
| Enclosure rating | NEMA Type 4X |
| Switch | DPDT, 1 Amp @ 30 VDC and 1 Amp @ 125/250 VAC |
| Terminals | Screw terminal strip, 12 to 22 AWG |
| Conduit | Two fittings, 3/4 in. – 14 NPT |
| Temperature | –35° to 66°C (–30° to 150°F) |
| Humidity | 85% RH at 86°F |
| Approvals | UL, Marine, CSFM, MEA |