Product details
The System Sensor 2W-B is a conventional two-wire photoelectric smoke detector from the i3 series, shipped as a plug-in detector head together with its mounting base. It is the photoelectric-only i3 model, with no thermal element, and is a common choice for offices, classrooms, corridors and other light-hazard spaces on conventional fire alarm panels.
Key features
- Photoelectric smoke sensing on a standard 2-wire initiating device circuit
- Plug-in head with Stop-Drop 'N Lock mounting, so the base can be wired at rough-in and the head fitted at trim-out
- Drift compensation and smoothing algorithms to reduce nuisance alarms from contamination and short-term interference
- Remote maintenance signalling and EZ Walk loop test when used with the 2W-MOD2 module or an i3-protocol panel
- Sensitivity can be read in %/ft obscuration with the SENS-RDR reader
Installation notes
Because the 2W-B is a two-wire device, alarm current is set by the panel's initiating circuit rather than by the detector. Check the panel's compatibility list for i3 2-wire detectors and the maximum number of detectors per zone before designing the circuit.
Also searched as: 2WB
Specifications
| Model | 2W-B (i3 series) |
| Sensing | Photoelectric (no thermal sensor) |
| Wiring | 2-wire, non-polarized |
| Operating voltage | 12/24 V nominal (8.5 V min, 35 V max) |
| Standby current | 50 µA average max; 100 µA peak |
| Alarm current | 130 mA max, limited by the control panel |
| Nominal sensitivity | 2.5%/ft |
| Operating temperature | 32°F to 120°F (0°C to 49°C) |
| Humidity | 0 to 95% RH, non-condensing |
| Wire range | 14 to 22 AWG |