Product details
The System Sensor 4WITAR-B is a four-wire i3 series photoelectric smoke detector with an isolated 135°F fixed thermal sensor, an 85 dBA sounder and a Form C relay, with base included. Smoke sounds the local horn and resets on its own without sending an alarm to the panel; only the heat sensor triggers a general alarm and switches the relay, which suits applications where smoke should alert occupants locally only.
Key features
- Isolated thermal design: smoke gives a local alarm, heat gives a panel alarm
- 85 dBA temporal tone sounder that can be synchronized with the RRS-MOD
- Form C relay transfers on a thermal alarm
- 135°F fixed, restorable heat element (not rate-of-rise)
- Drift compensation and 41°F freeze trouble signal
Compatibility
The four-wire relay base also accepts the 4WTR-B and 4WTAR-B heads. If smoke alone should alarm the panel, choose the 4WTAR-B, which has a non-isolated thermal sensor.
Also searched as: 4WITARB
Specifications
| Model | 4WITAR-B (i3 series) |
| Wiring | 4-wire |
| Operating voltage | 12/24 V nominal (10 to 35 VDC) |
| Current | 50 µA standby; 50 mA alarm |
| Smoke sensitivity | 2.5%/ft |
| Form C relay | 2 A at 30 V AC/DC |
| Alarm contacts | 0.5 A at 30 V AC/DC |
| Sounder | 85 dBA, ANSI S3.41 temporal |
| Dimensions with base | 5.3" diameter x 2.0" high |