Product details
The System Sensor 5601P is a single-circuit 5600 Series mechanical heat detector with a normally open contact, activating at a fixed 135°F (57°C) or on a rapid rate of rise. Its plain housing carries no exterior lettering, which is why it is offered for residential settings. Like the rest of the series it is intended for property protection in places where smoke detectors are unsuitable, such as garages, attics, kitchens and mechanical rooms.
Key features
- Combination fixed-temperature and rate-of-rise operation
- Rate-of-rise element is restorable for field testing
- A collector drops from the unit on activation to show which detector operated
- Reversible bracket for flush or surface back box mounting
- Plain housing with no exterior markings
Installation notes
The fixed-temperature element is not restorable; once it operates the detector must be replaced. Since the housing is unmarked, record the model at commissioning so it is not confused with other 5600 models.
Specifications
| Model | 5601P |
| Circuit | Single, normally open |
| Alarm temperature | 135°F (57°C) |
| Rate-of-rise | 15°F (8.3°C) per minute |
| UL spacing | 50 x 50 ft (15.2 x 15.2 m) on a 10 ft ceiling |
| Max installation temperature | 100°F (38°C) |
| Contact ratings | 3 A at 6-125 VAC; 1 A at 6-28 VDC; 0.3 A at 125 VDC; 0.1 A at 250 VDC |
| Dimensions with bracket | 4.57" (11.6 cm) diameter x 1.69" (4.3 cm) high |
| Weight | 6 oz (170 g) |
| Listing | UL 521 |