Product details
The VESDA VHX-0420 is the standard (unenclosed) Modbus Type 3 High Level Interface for VESDAnet aspirating smoke detection networks. It acts as a proxy for every VESDA device on the network, so a building management system or fire panel can read status and write control and configuration through Modbus registers. It connects to the network through a VESDAnet socket interface.
Key features
- Supports up to 100 VESDA detectors on one VESDAnet network
- Reports alarm and fault status, detailed faults, smoke level and alarm thresholds
- Passes reset, disable, silence, alarm test and normalize commands
- Covers VESDA VLP, VLS, VLC, VLF, VLI and VFT-15, plus VESDA-E VEU, VEP, VES and VEA
- Supplied with VESDAlink RS-232 9-way and VESDAnet RS-485 15-way cables
Ordering note
The VHX-1420 is the same Type 3 interface in a wall-mounted metal box with a built-in VESDAnet interface. The earlier VHX-0400 (Type 1) and VHX-0410 (Type 2) are limited to 40 detectors and do not support VESDA-E.
Specifications
| Model | VHX-0420 |
| Type | Modbus Type 3 High Level Interface, standard |
| Supply | 24 VDC |
| Quiescent current / power | 70 mA / 1.68 W |
| Detectors supported | Up to 100 per VESDAnet network |
| Dimensions | 188 x 98 x 40 mm (7.4 x 3.9 x 1.6") |
| Weight | 0.4 kg (0.9 lb) |
| Included cables | VESDAlink RS-232 9-way; VESDAnet RS-485 15-way |